Testing a String of Serially Wired LEDs
Let’s say one of the strings of lights is not working correctly—how do you troubleshoot it? This FAQ is for series-wired LEDs.
Tools required:
- OJ-606 short (3 pcs)
Installed Switches:
- AL-WS-DR1, AL-WS-Bath: Turn the switch on, set to minimum—this will supply about 20 mA for testing.
- AL-WS-DR2W, DR2C, DR2 with firmware 23 or later: Enter Test Mode to supply 7 mA for testing.
Entering Test Mode:
- Break the circuit by disconnecting one LED in the string that is not working.
- Turn the switch off.
- Wait 6 seconds.
- Turn the switch on.
- Wait 6 seconds—the switch outputs 7 mA on the LED output(s) with no complete circuit.
Setting up the Test:
- Let’s say you have 4 LEDs in a string.
- We are only testing series wiring today.
- Disconnect 3 LEDs and bypass them:
- For tunable white: connect the male/female OJ-606 together.
- For fixed color: connect the OJ-606 short in place of the LED.
- Leave just one connected so the loop has only one active LED.
Testing the LEDs:
- Turn the LEDs off, wait 6 seconds, then turn them back on.
- The string(s) being tested should pulse for the calibration sequence.
- At the end of calibration, the connected LED should dim from off to full brightness. If not:
- Remove the LED, turn the light off (6 seconds), on (6 seconds), then off.
- Replace that LED, mark it, and install a fresh LED. Restart testing.
- If all LEDs fail, there is likely a bad wire.
- Repeat by connecting 2 LEDs, then 3, then 4, returning to the first step each time you add another LED.
Testing the Wiring (requires a voltmeter and a screwdriver):
- Remove the switch from the wall.
- Use a lever nut to short the wires that go up to the LEDs in the ceiling.
- Go to the first LED and measure the loop resistance; it should be less than 1 ohm. If it is greater, find the break.