UL924 Emergency Lighting Method
ATX LED supports emergency lighting two ways
Residential Lighting Systems
- Our Struct12 supports a UPS input at 44–52 V to power lights and DC loads when 120 VAC fails, supplementing its redundant power supplies.
- Struct12 detects mains failure and commands all lights to operate at 5–10% output, extending battery life while ensuring illumination.
- Struct12 issues a Group ON for group 15: any light in this group dims to 10%, overriding wall switches to guarantee light even if switches are inaccessible.
Commercial Lighting Systems
- Our AL-ATS-8-7D PoE switch senses 120 VAC loss and downgrades PoE outputs from 802.3at to 802.3af.
- Our AL-AT-TW1 PoE LED driver then drops from full power to 5% mode, further extending run time.
- In 802.3af mode, any user switch is overridden and all lights remain at 5% output.
- By default all ports switch to 802.3af, but an admin can assign individual ports to off-state instead of 802.3af to maximize battery endurance.